Sweep Frequency Response Analysis (SFRA) Test of Transformer: Complete Guide

SFRA Thumbnail

Sweep Frequency Response Analysis or SFRA is a test which is used to assess the mechanical integrity of the transformer’s main part which is core, winding and clamping structure by injecting low voltage signals from few Hz to several MHz and measuring the response of transformer at various frequencies.

Core idea of SFRA

Each transformer behaves like a complex network of inductance, capacitance and resistance. Together it forms a unique electrical fingerprint. The SFRA test kit injects low-voltage signal that sweeps from a low frequency of 20 Hz to 2 Mhz and measures the response of the transformer. The measurement or curve, which is gain (dB) vs frequency (Hz) is plotted by the tester and is compared to the factory baseline records or previous test history.

Any mechanical deformation of the main part of the transformer changes the internal R-L-C network which shifts the frequency signature.

SFRA Test equipment

The SFRA test setup is built around a precision analyser, which injects and measures the frequency response with very high repeatability. The signal generator of the test equipment produces low voltage swept sine wave across wide frequency spectrum, which is recorded by the reference channel. The measurement channel captures the transformer’s response. The analyser compares both the signals and compute the transfer function.

SFRA typical connection

Shielded coaxial cables are used in the test for preventing electromagnetic noise and ensuring stable impedance. A laptop with dedicated analysis software which has the baseline signature stored in it, overlays the past results over the current curve and highlights the deviation.

SFRA Test connections

Open circuit Connection

End to End (1U-2u): It excites the full winding resistance and detects axial displacement of the winding, winding compression or loosening, hoop buckling after short circuit, turn to turn deformation, winding collapse, core movement, clamping pressure change, bad lead connection.

Inter phase (1U-1V): It excites the mutual coupling between adjacent windings and detects radial displacement between phases, phase to phase winding movement, interphase insulation deformation, uneven clamping of winding assembly, core asymmetry, winding tilt.

Diagonal phase (1U-2v): It excites the longest coupling path and help detect the global winding distortion, major mechanical displacement, core-frame shift, structural looseness.

Short circuit SFRA

In this connection the HV or LV windings are shorted which supresses the magnetizing effects and forces the measurement to be dominated by leakage impedance and mechanical coupling between the windings. It detects radial winding displacement like HV bulging, LV winding collapse, loss of radial spacers.

Any change in the distance between HV and LV alters the mutual coupling. Short circuit SFRA detects the compression between windings, insulation barrier displacement, crushed pressboard cylinders, reduced mechanical stiffness, degraded clamping pressure.

Feature / Fault TypeOpen-circuit SFRAShort-circuit SFRA
Main winding geometry fingerprintPrimary detectionSecondary
Axial winding displacementGood sensitivityExcellent sensitivity
Radial winding movementModerateVery high sensitivity
Inter-winding spacing changeLimitedPrimary detection
Turn buckling / hoop deformationModerateExcellent
Short-circuit mechanical damageVisibleHighly visible
Core displacementDetectable (low frequency band)Minimal sensitivity
Clamping structure loosenessDetectableDetectable
Lead movement / tap lead shiftHigh-frequency bandLimited
Core-to-frame structural issuesDetectableNot targeted
Transport shock damageDetectableConfirmatory
Leakage inductance variationIndirectDirect measurement
Magnetizing branch behaviourVisibleSuppressed intentionally

Test procedure

Step1: Deenergize the transformer and isolate it by disconnecting the winding terminals.

Step 2: Clean the bushing terminals.

Step 3: connect the SFRA leads as per test plan.

Step 4: Run Sweep phase by phase.

Step 5: Save reference traces and label data correctly.

Step 6: Repeat for all windings.

Test result evaluation

The SFRA interpretation is comparative and not absolute. The analyser does not provide pass or fail resistance values, instead the diagnosis is based on the curve matching to the factory acceptance test and any deviation indicates a mechanical or structural change. Evaluation can also be done by phase-to-phase comparison of the same transformer. Consistency is of more importance here than magnitude.

SFRA test traces

Fault localization by frequency band

Frequency regionSensitive componentsTypical fault
Low frequencyCore & clamping structureCore displacement, loose clamps
Mid frequencyMain winding bodyAxial/radial winding deformation
High frequencyLeads & stray capacitanceLead movement, insulation spacing change

Red flags in SFRA traces

SFRA red flagWhat it indicates electricallyLikely mechanical issue
Shift in resonance frequencyChange in inductance/capacitance networkAxial or radial winding displacement, core movement
Amplitude deviation between phasesLoss of symmetry in transfer functionUneven clamping, phase-to-phase movement
Missing resonance peaksSuppressed natural resonancesCollapsed spacers, winding compression, structural damage
Flattened peaksReduced mechanical stiffnessLoosened winding assembly, degraded clamping pressure
Increased dampingHigher energy absorptionFree winding vibration, friction from shifted parts
Sudden curve discontinuityLocal impedance changeBroken support, conductor shift, internal mechanical fracture

This article is a part of the Testing and commissioning page, where other articles related to topic are discussed in details.

Leave a Comment