Electrical Clearance: Detailed Guide

The minimum distance or gap that is required between two conducting parts, without causing any electrical flashover, is known as electrical clearance. Electrical clearance is a function of the implied voltage or potential difference between the two conductors.

Electrical Clearance

If the voltage between two conductors is more, then the required electrical clearance will be higher. In case the gap is less, charges from one conductor will flow to another conductor, making the other one charged as well.

Table of Contents

Electrical clearances are important in a substation for maintaining the safety of personnel, safety of the equipment, and the reliability of the operation.

Types of electrical clearance

Vertical clearance: It is the minimum vertical distance between the charged conductor and the ground, for example the the clearance between the equipment top and the bus bar, charged overhead line, and the tower structures, the gap between the ground wire and the top conductor.

Horizontal clearance: It is the minimum horizontal distance between two charged conductors or between charged conductors and a grounded structure, for example, the phase-to-phase clearance, phase-to-ground clearance, or equipment-to-equipment distance.

Classification of Electrical Clearance based on Function

Phase-to-phase clearance: As the different phases incorporate a potential difference between them, reliable operation will cease to exist if they are electrically shorted. Therefore, the phase-to-phase clearance must be maintained. It is a function of system voltage and insulation.

Bay width

Phase-to-earth clearance: It is the minimum distance from a phase conductor to a grounded structure. In case this minimum distance or gap is not maintained, current may flow to the grounded part, causing an earth fault to exist in the line. If maintained properly, it prevents arcing during normal and faulty conditions.

Sectional Clearance: These are the minimum distances between the equipment, like the Circuit breaker, isolator, current transformer, and busbar, which are essential for safe operation of the equipment, as well as to provide safe working of personnel under the charged condition. The distance between the equipment in any one phase must be higher than the safe phase to earth clearance, and the foundation of the equipment must not overlay.

Voltage Level33KV66KV132KV220KV400KV800KV
Bay WIdth5.5 m7.6 m12 m16m24 m45 m
Phase-to-Phase clearance0.320 m0.630 m1.3 m2.1 m4.2 m9.4 m
Phase to earth clearance0.320 m0.630 m1.3 m2.1 m3.5 m6.4 m
Sectional Clearance2.8 m3.1 m4 m5 m6.5 m10.3 m
Equipment Height (Live to Ground)3.7 m4 m4.6 m5.5 m8 m14 m
Main Busbar height from Ground5.5 m6 m9 m11.7 m15 m27m

Height of the lowest portion of the insulator supporting the live conductor, equipment parts, etc, where it meets the earthed metal structure, is 2.440 m for all systems.

The distance between conductors is dependent on the bay width, short circuit forces, and wind swings. It is normally shown on the plan drawing, whereas equipment-to-equipment distance is shown in the sectional elevation.

Electrical clearance is also required when power lines cross each other in order to avoid any flashover or arcing between the power lines of different voltage levels. Also, overhead lines sag because of heat resulting from high current carrying and atmospheric temperature, as well as ice loading. In order to eliminate the risk of contact minimum vertical clearance has to be met.

Minimum electrical clearance between the AC power lines crossing

System Voltage11 to 66 KV132 KV220 KV400 KV800 KV
11 to 66 KV2.44 m3.05 m4.58 m5.49 m7.94 m
132 KV3.05 m3.05 m4.58 m5.49 m7.94 m
220 KV4.58 m4.58 m4.58 m5.49 m7.94 m
400 KV5.49 m5.49 m5.49 m5.49 m7.94 m
800 KV7.94 m7.94 m7.94 m7.94 m7.94 m

Minimum electrical clearance between the AC and DC power lines crossing

System Voltage100 KV DC200 KV DC300 KV DC400 KV DC500 KV DC600 KV DC
11 to 66 KV3.05 m4.71 m5.32 m6.04 m6.79 m7.54 m
132 KV AC3.05 m4.71 m5.32 m6.04 m6.79 m7.54 m
220 KV AC4.58 m4.71 m5.32 m6.04 m6.79 m7.54 m
200 KV DC4.71 m4.71 m5.32 m6.04 m6.79 m7.54 m
400 KV AC5.49 m5.49 m5.49 m6.04 m6.79 m7.54 m
400 KV DC6.04 m6.04 m6.04 m6.04 m6.79 m7.54 m
500 KV DC6.79 m6.79 m6.79 m6.79 m6.79 m7.54 m
600 KV DC7.54 m7.54 m7.54 m7.54 m7.54 m7.54 m
800 KV DC7.94 m7.94 m7.94 m7.94 m7.94 m7.94 m

Overhead lines crossing buildings:

It is advisable not to start any construction works under an overhead transmission line; however, if it exists, it must be ensured that a vertical clearance of 3.7m minimum exists for lines between 650 Volts to 33 KV. For lines exceeding 33 KV, a vertical clearance of 3.7 m should be maintained, along with 0.3 m for every additional 33KV thereof.

While the horizontal clearance in case of overhead transmission line and buildings should be 1.2 m up to 11KV and 2 m up to 33KV. In case of extra high voltage lines above 33 KV, 0.3 m should be added to the initial clearance of 2 m for every additional 33 KV.

In case of HVDC systems and buildings, the vertical and horizontal clearances must be

DC VoltageVertical clearanceHorizontal clearance
500 KV DC9.1 m7.4 m
600 KV DC10.3 m8.6 m
800 KV DC12.4 m10.7 m

Electrical clearance on the river crossing must be above 3050 mm above the highest flood level recorded.

Minimum clearance over telecom lines for PTCC clearance must be

Voltage LevelMinimum clearance
132 KV AC2745 mm
220 KV AC3050 mm
400 AC4880 mm

Minimum electrical clearance for a Railway crossing

Voltage LevelMinimum Vertical Clearance under maximum sag of the bottom conductor
33 KV and 66KV14.10 m
132 KV14,60 m
220 KV15.40 m
400 KV17,90 m
500 KV19.30 m
800 KV23.40 m

Leave a Comment